    The MSP Series is a modular sequencing panelboard system built on reliable Square D remote-controlled breakers for simplified one-touch power control. Designed for permanent AVL installations, it streamlines deployment with simple setup and provides robust protection features like brownout and emergency shutdown.

    Request a Quote

    Request A Quote

    Request more information about this product or speak directly with our sales team today.

    This field is for validation purposes and should be left unchanged.
    We route your message directly to the right team so you don’t get bounced around.


    The MS Series provides modular sequencing for power control using breaker or relay based panels. Engineered to protect sensitive audio and video systems from damaging inrush currents, these panels ensure a safe, controlled startup and shutdown sequence for all connected equipment.

    Engineered for Simplicity and Reliability

    Platform

    Square D Breakers

    Control

    Contact Closure

    Sequencing

    On and Off

    Protection

    Brownout, E-Shed

    Setup

    No Commissioning
    SEQUENCING SYSTEM

    Simplified, reliable power sequencing for any venue.

    The LynTec MSP Series simplifies power sequencing for complex AVL systems by integrating control and distribution into a single, robust panelboard. Built on the proven reliability of Square D motorized breakers, the MSP provides sequential turn-on and reverse-sequence-off with a selectable step rate, all managed through simple contact closure inputs. This one-touch system control eliminates the need for complex programming or on-site commissioning, reducing installation time and labor costs for integrators.

    Engineered for long-term performance, the MSP runs cool and efficiently with no holding current required to maintain its state. Standard features include automatic load shedding for emergency shutdown and brownout protection to safeguard connected processors and sensitive electronics. With options for isolated technical grounding, bolt-on breakers, and in-panel SurgeX surge elimination, the MSP system can be configured to meet the specific protection and power quality needs of any performance venue.

    SYSTEM INTEGRATION

    Integrate the MSP system with your facility.

    The MSP series is designed to work with standard facility control and protection systems.

    Third-Party Control Systems

    Integrates with any system capable of providing a dry contact closure, including automation systems, key switches, and schedulers.

    Emergency Power Off Systems

    Standard automatic load shedding allows for seamless integration with fire alarm and emergency override systems for life safety compliance.

    SurgeX In-Panel Modules

    Optional modules drop directly into the panel to provide robust, industrial-grade surge protection for all connected circuits.

    Isolated Grounding Infrastructure

    An optional dedicated cabinet provides a clean, isolated ground for sensitive audio and video systems, reducing noise and interference.
    CONFIGURATION OPTIONS

    Built to your project’s specs.

    Every MSP panel is configured for your specific installation. Expand each category for available options.
    Available Models

    MSP panels are available in several configurations based on the main electrical service rating.

    • MSP 139 and 338 Series: Designed for installations with main breakers rated less than 100A.
    • MSP 141 and 341 Series: Configured for larger installations with main breakers rated greater than 100A.
    Breaker Configurations

    The system supports multiple breaker types to match your circuit requirements.

    • Pole Count: Accommodates one, two, or three-pole motorized breakers for flexible circuit control.
    • Mounting Style: Available with traditional plug-on breakers or optional bolt-on breakers for enhanced connection security.
    Control

    The MSP system is designed for simple, reliable external control integration.

    • Inputs (Standard): Dry contact closure inputs provide the primary method for triggering on and off sequences.
    • Outputs (Optional): Contact closure outputs can be added to any panel to provide status feedback to third-party control systems.
    Add-Ons & Accessories

    Enhance your panel with integrated modules for power quality and specialized grounding.

    • SurgeX Surge Elimination: Optional in-panel modules provide industrial-grade protection against damaging power surges and transients.
    • Isolated Technical Ground: An available dedicated cabinet provides an isolated ground to reduce electrical noise for sensitive audio and video systems.
    • IPC Integrated Power Center: Combines an isolation transformer and breaker panel into a single floor-standing unit for maximum power quality and density.
    ONE-TOUCH CONTROL

    Build Your MSP Sequencing Panelboard System

    The MSP is a modular system. Select a primary panel and any required add-ons to create a customized sequencing solution for your AVL installation.
    Required

    MSP Sequencing Panelboard

    The core of the system, providing sequenced power control using remote controlled Square D breakers. Available in multiple configurations based on main breaker amperage.
    WHY LYNTEC

    Engineered for simplicity and long-term reliability.

    • Built on the proven Square D motorized breaker platform
    • Simple setup with no on-site commissioning required
    • Energy efficient design runs cool for a longer service life
    • US-based application engineering and support
    FEATURES

    MSP Series System Features

    An overview of the standard capabilities and optional configurations available for the MSP sequencing panelboard system.
    CAPABILITIES

    Features

    Sequential Power Control

    Provides sequential turn-on of electrical circuits and a reverse sequence for power-off.

    Selectable Step Rate

    A standard selectable delay between sequencing steps allows for system customization.

    Simple Setup

    Engineered for straightforward installation without requiring on-site commissioning.

    Energy Efficient Operation

    Requires no holding current to maintain state, ensuring the panel runs cool and lasts longer.

    Automatic Load Shedding

    A standard feature for integration with emergency shutdown and fire alarm systems.

    Brownout Protection

    Protects sensitive processors and electronics from under-voltage conditions.

    Contact Closure Control

    Standard inputs allow for simple one-touch system control from third-party systems.

    Optional SurgeX Protection

    Integrate industrial-grade surge elimination directly into the panelboard.
    01

    One-Touch System Control

    Simple contact closure inputs provide sequential turn-on and reverse-sequence-off for the entire system, eliminating the need for complex programming or specialized on-site commissioning.
    • Standard contact closure inputs
    • Selectable delay step-rate
    • No on-site commissioning required
    02

    Built on a Trusted Platform

    The MSP series utilizes remote-controlled motorized breakers from Square D, providing unmatched reliability and a long service life for mission-critical power infrastructure.
    • Time-proven Square D motorized breakers
    • Energy efficient design with no holding current
    • Spacious panelboard for easier installation
    03

    Integrated System Protection

    Standard protection features safeguard connected equipment against common power issues, ensuring system stability and protecting your investment in sensitive AVL electronics.
    • Automatic load shedding for emergency shutdown
    • Brownout (under-voltage) protection
    • Optional SurgeX in-panel surge elimination
    SPECIFICATIONS

    MSP Series System Specifications

    Review the electrical, control, and protection specifications common across the MSP Series platform.
    PRIMARY PANELS

    MSP Sequencing Panelboards

    The core of the system, providing sequenced power control. Available in multiple configurations based on main breaker amperage.

    Model Main Breaker
    MSP 139-xx < 100A
    MSP 141-xx > 100A
    MSP 338-xx < 100A
    MSP 341-xx > 100A

    Shared MSP System Specifications

    Technical details and capabilities common across the MSP Series of sequencing panelboards.

    Control and Sequencing

    • Primary Control Method
      Contact Closure Input
    • Sequencing
      Sequential On, Reverse Sequence Off
    • Step Rate Delay
      Selectable
    • Optional Outputs
      Contact Closure

    Protection

    • Under-Voltage
      Brownout Protection Standard
    • Emergency Off
      Automatic Load Shedding Standard
    • Surge Protection
      Optional SurgeX In-Panel Module

    Electrical Options

    • Breaker Platform
      Square D Motorized
    • Breaker Types
      1, 2, or 3-Pole
    • Breaker Mounting
      Plug-on (Standard), Bolt-on (Optional)
    • Grounding
      Optional Isolated Technical Ground
    • Neutrals
      200% Neutrals Standard

    Questions or Concerns?

    Let us know, we’re here to help! Contact Us

    PRODUCT SUPPORT

    MSP Series System Support

    Find documentation, application notes, and answers to common questions for the MSP Series.
    VIDEOS

    Setup & training video series.

    EPISODE 1 / 5 · 9:27
    Building a Controllable Breaker Panel Part Number
    FAQ

    FAQs about the MSP Series

    Can the MSP support isolated ground systems for audio?

    Yes, the MSP series offers an optional dedicated cabinet for isolated technical grounding. This helps reduce electrical noise for sensitive audio, video, and recording equipment.

    Does the MSP panel require on-site programming or commissioning?

    No, the MSP system is designed for simple setup and does not require any on-site commissioning or specialized programming, which helps reduce installation time and costs.

    How do I choose the right MSP model for my project?

    Model selection is primarily based on the main breaker amperage of your electrical service. Panels are available for services both under and over 100A. Contact a LynTec engineer to spec the correct configuration.

    How is the MSP system controlled?

    The MSP system is controlled via standard dry contact closure inputs. This allows for simple one-touch control from third-party systems like key switches, automation systems, or emergency overrides without complex programming.

    Is there a ‘ZipOn’ function for fast system activation, for example, to get an arena paging system online within 15 seconds?

    We never thought of it as a ZipOn, but we can accomplish that function. The MS series modular sequencer flexibility makes this fast turn-on function possible. The MS series STEP RATE may be set at 1/8, 1/4, 1/2 or 1 second. 80 circuits would require two MSP or MSLC 341-48 cabinets. Each cabinet holds up to 41 motorized breakers. Each cabinet has 4 daisy-chained, 6 step sequencer boards. Each step controls two motorized breakers, so we have 24 steps per cabinet. By installing both the 1/4 and 1/2 second STEP RATE jumpers we can set the step rate to 1/8 second. Each of the two cabinets with 24 steps, will take 3 seconds to turn on. (24 steps x 1/8 sec. = 3 sec.)

    By using only 6 of the 15-second design target, there will still be some time that may be used for front end settling by setting the delay between steps 1 and 2 of the first board to 4 or even 8 seconds. A variation would be to turn on each step at 1/4 second with a settling time delay of 2 seconds for a total turn-on time of 14 seconds. (48 steps x 1/4 =12 sec. + 2 sec. settling time = 14 sec.)

    For larger systems, we can turn on up to 5 sequencing systems in parallel to keep the turn-on time to a minimum. For instance: A stadium has a small MSLC panel in the control room with 24 circuits. With a 4 second settling time delay it requires 5.5 seconds to turn on. (12 steps x 1/8 sec = 1.5 sec + 4 sec. settling time = 5.5 sec.) By series-parallel connecting the daisy chain connections to five MSLC/MSP 341-48 panels we can turn on a 229 circuit system in 8.5 seconds. (Front end MSLC = 5.5 sec. + five parallel connected MSLC or MSP 341-48s, each requiring 3 sec. = 8.5 sec. total turn-on time)

    What kind of circuit breakers does the MSP system use?

    The MSP series is built exclusively on the reliable, time-proven Square D motorized circuit breaker platform, ensuring long-term performance in demanding environments.

    What protection features are included with an MSP panel?

    Every MSP panel includes standard brownout (under-voltage) protection and automatic load shedding for emergency shutdown. Optional SurgeX in-panel modules can be added for industrial-grade surge elimination.

    Ready to spec your next install?